Checking the design

Hydraulic calculations

The Studio calculates the system you actually drew — the same pipe, fittings and elevations. There is no separate hydraulic model to keep in step.

WhatWhere you'll find it
Water supply · fire pumpCtrl+Shift+W · Ctrl+Shift+P, or the SUPPLY / HYDRAULICS toolbar groups
Remote area boundaryThe remote-area button in the HYDRAULICS group
Live calculations on/offThe Live pill in HYDRAULICS
ResultsSide panel → Analysis → Calc, Demand, Nodes, Links, Runs, Remote Areas, Warnings
Node tags on the planView → Hydraulic Node Tags
Printed calcsReports → Hydraulic Calc Package / Print…Remote Area Calcs

1. Give it a supply

Place a water supply ball (Ctrl+Shift+W) where the supply enters, and edit its curve — static, residual and flow from the flow test. If there is a pump, place a fire pump element (Ctrl+Shift+P) and right-click it to Adjust pump curve…. Flip pump reverses suction and discharge if you drew it the other way round.

Supply curves clamp at zero. Ask for more flow than the test measured and the answer is “no pressure available” — never a negative number pretending to be a result.

2. Draw the remote area

Pick the remote-area tool from the HYDRAULICS group and outline the area. The boundary snaps to the midline between heads, so it lands where a reviewer expects it rather than through a sprinkler.

3. Decide which heads flow

Every sprinkler carries its own flow setting, and every part of the program — the remote-area calc, the project-wide preview, and the printed report — resolves it the same way, so they cannot disagree.

A head can also carry a minimum to flow — either a minimum psi or a minimum gpm, never both (if both somehow get set, psi wins). A minimum is a floor on a head that is already flowing; it never turns a dry head on. Flow and pressure stay tied through the head's K-factor, the same way the NFPA 13 7 psi minimum operating pressure is applied.

Set it from the sprinkler's Properties panel, or right-click in the drawing → Set Flow → Open / Closed / Automatic / Minimum to Flow… / Clear minimum. Either route works on a whole multi-selection in one undo and keeps your selection.

A project with no remote area has nothing to scope to, so it flows every head that has demand, minus the closed ones.

4. Run it

5. Read the results

The Analysis tab in the side panel carries the whole answer:

View → Hydraulic Node Tags puts the node numbers on the plan in hex tags — prefix, starting number, size and colour are all settable, they can carry leader lines, and you can drag them clear of your linework.

Friction losses

Valves and flex drops carry their own losses, entered as an equivalent length or a custom curve. A flex drop's loss is on its right-click menu alongside its length.

Printing the calc

The printed layout is being matched to the calc report format reviewers already know.

Where this is still moving. The solver and the reports are real and in daily use, but calc-report formatting is still being brought to parity, and fluid delivery time is designed but not yet a feature you can run. Check the numbers before you stamp anything — that is true of every tool, and doubly true of an alpha.