Checking the design

Analysis, compliance & takeoff

The Analysis tab is where the Studio tells you what it thinks of your drawing — and where the numbers for buying and building it come from.

WhatWhere you'll find it
Everything on this pageSide panel → Analysis tab
Exports of the same dataReports menu
Performance modeDisplay & Defaults → Perf

Live checking

Analysis runs in the background and never blocks your drawing. Spacing, coverage, obstruction and general lint checks all produce plain-language issues rather than error codes.

On a big job the Studio switches itself to Draft performance mode, which defers the heavier live work. Switch Perf back to Full in Display & Defaults when you want everything current.

The compliance tabs

Quantities and fabrication

Read the fabrication warnings. A size that is not in the takeout catalog gets no takeout — a full-length, field-trimmable cut — and says so. A spool whose takeouts exceed the pipe length is flagged “cannot be fabricated as drawn”. Neither is silently fudged, which is the point.

Getting it out of the program

The Reports menu writes the same information to files:

Some of these are behind build flags and may not be in your copy yet.

A workflow that keeps you honest

  1. Lay out heads, then clear Issues while it is only heads — spacing and coverage problems are cheap to fix before pipe exists.
  2. Route pipe, then clear Clashes.
  3. Set the remote area and supply, run the hydraulics, clear Warnings.
  4. Only then generate hangers, bracing and dimensions — they are the parts most expensive to redo.
  5. Take off quantities last, from a drawing that has already passed the other four.